Refrigerated Air Dryer

Why Compressed Air Filter

Refrigerated Compressed Air Dryers are one of the most common used types of Air Dryers. It is simple in design, requires very little maintenance and cost effective. Generally where the buyers don’t have special requirements, like an ultra-low dew point – The refrigerated Air Dryer is the suitable option to protect the tools and equipments.

Working Principal

Saturated Compressed Air enters the Pre Cooler within which it is cooled by exchanging heat outgoing chilled air. The inlet Air is further cooled in the super cooler (Evaporator) by refrigerant. In the Evaporator heat transferred from the compressed air to refrigerant. This process cooled the air and reduces the capacity to hold water vapor resulting in moisture condensation. This condensed moisture is removed from the air stream by an in-built moisture separator and automatic drain valve. Lastly before reaching the application cold compressed air passes through pre cooler, where the cold air re-heated. Refrigerant Compressor and condenser supply the cooled refrigerant to evaporator through expansion device. The Hot gas by-pass valve balance the operation of refrigerant system to compressed air cooling load.

Features

Technical Specifications

Model

Inlet Flow

Power Supply

Rated Power (kW)

End Connection

cfm

M3/Hr

230 VAC, 50 Hz, 1Ø

AC

ZD 20

20

34

0.13

½’’

BSP F

ZD 40

40

68

0.2

¾’’

ZD 60

60

102

0.33

¾’’

ZD 80

80

136

0.42

1’’

ZD 100

100

170

0.6

1’’

ZD 120

120

212

0.7

1’’

ZD 150

150

255

0.85

1 ½’’

ZD 200

200

340

1.12

1 ½’’

ZD 250

250

425

1.35

1 ½’’

ZD 300

300

510

415 V AC, 50 Hz, 3Ø

1.6

2’’

NB

( FLANGE IS :

6392,

T -17)

ZD 400

400

680

1.9

2’’

ZD 500

500

850

2.2

3’’

ZD 600

600

1020

2.7

3’’

ZD 750

750

1275

3.1

3’’

ZD 1000

1000

1700

4.4

4’’

*use Correction Factor for other range.

Correction Factor

Inlet Air Temperature

Temper Inlet Air Temperature ( 0c)

30

35

40

45

50

55

60

Correction Factor (C1

1.63

1.38

1.2

1

0.8

0.62

0.5

Inlet Air Pressure

Air Pressure bar (g)

4

6

7

8

10

12

16

Correction Factor (P1

0.62

0.87

1

1.07

1.22

1.35

1.63

Ambient Temperature

Temperature (°C)

30

35

40

45

50

55

Correction Factor (C2)

1.12

1.06

1

0.94

0.88

0.75